*PUMP LEAKAGE - MAIN PROBLEM*

- *Seal fail*: mechanical seal worn
- *Gasket damage*: joint leaking
- *Shaft wear*: gap creates leak
- *Fix*: change seal, tighten, align shaft #Pump
https://www.instagram.com/reel/Dcm5jbXJLVf/?igsi=OGlkZ3dsNDZnNDBh
❤1
*PUMP PRIMING*

- *What*: fill pump with water to remove air
- *Why*: air stops suction, pump runs dry
- *How*: close delivery, open vent, pour water till full
- *Done when*: water comes from vent, no bubbles #Pump
https://www.instagram.com/reel/DcknuPUpd6G/?igsi=MTAwbjUzaW91bm5kbQ==
❤3
This media is not supported in the widget
VIEW IN TELEGRAM
FIRE Pressure Calculation ‼️✅
.
.
#fire
❤5
Comment ur answer ❓
❤1
Which purpose use this helmet❓❓❓
.
.
#helmet
❤2
Fire-fighting and Fire Alarm system 👷🏻🧰
Photo
❓ FIRE PUMP CALCULATION:

How do you calculate Fire Pump Flow Rate?

Formula:

Total Flow =
Sprinkler Demand + Hydrant Demand

Example:

Sprinkler Flow = 1,000 L/min
Hydrant Flow = 500 L/min

Total Flow =
1,000 + 500

= 1,500 L/min

Convert to m³/hr:

1,500 × 60 ÷ 1,000
= 90 m³/hr

✅ Fire Pump Flow Rate = 90 m³/hr

Final pump flow should be determined from the applicable fire-protection standard and hydraulic calculation.

#FirePump #FirePumpCalculation #FireProtection #MEPEngineering #PumpCalculation
❤1
❓ CHILLER CALCULATION:

How do you calculate Chilled Water Flow Rate?

Formula:

Q = Cooling Capacity ÷ (ρ × Cp × ΔT)

Example:

Cooling Capacity = 350 kW
Water Density (ρ) = 1000 kg/m³
Cp = 4.186 kJ/kg·K
ΔT = 5°C

Mass Flow =
350 ÷ (4.186 × 5)

≈ 16.73 kg/s

Convert to m³/hr:

16.73 × 3.6
≈ 60.2 m³/hr

✅ Chilled Water Flow Rate ≈ 60.2 m³/hr

This calculation is useful for preliminary chiller, chilled water pump and pipe sizing.

#ChillerCalculation #HVAC #MEPEngineering #ChilledWater #HVACDesign
❤3👍2
3 Main components of the fire Hydrant System?
1 ...
2 ...
3 ...